Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-102075 Overview
CVE-2026-102075 is a stack-based buffer overflow [CWE-121] affecting multiple Siemens APOGEE and TALON building automation controllers. The affected web service does not properly validate user input during multipart HTTP request handling. An unauthenticated remote attacker can exploit this flaw over the network to trigger a denial-of-service condition on the device.
Critical Impact
An unauthenticated attacker reachable over the network can crash the controller web service, disrupting building automation functions until the device recovers or is restarted.
Affected Products
- APOGEE MBC (PPC) BACnet and P2 Ethernet (all versions)
- APOGEE MEC (PPC) BACnet and P2 Ethernet (all versions)
- APOGEE PXC Compact and Modular BACnet (all versions prior to V3.5.7); P2 Ethernet variants (all versions prior to V2.8.21)
- TALON TC Compact and Modular BACnet (all versions prior to V3.5.7)
Discovery Timeline
- 2026-10-13 - CVE-2026-102075 published to NVD
- 2026-10-15 - Last updated in NVD database
Technical Details for CVE-2026-102075
Vulnerability Analysis
The vulnerability resides in the embedded web service running on affected APOGEE and TALON controllers. The service parses multipart HTTP requests but fails to validate the length or structure of user-supplied input before copying it into a fixed-size stack buffer. This condition is classified under [CWE-121] (Stack-based Buffer Overflow).
Successful exploitation causes the web service process to crash, resulting in a denial of service. The Siemens advisory indicates the impact is limited to availability. Confidentiality and integrity are not affected based on the CVSS vector. The EPSS score of 0.573% (percentile 46.177) as of 2026-10-16 reflects a low near-term probability of observed exploitation, though network-reachable controllers remain exposed.
Root Cause
The web service's multipart handler lacks bounds checking on parsed input fields. Oversized or malformed multipart segments overflow a stack buffer and corrupt execution state, terminating the service.
Attack Vector
An attacker sends a crafted multipart HTTP request to the controller's web interface over the network. No authentication, user interaction, or elevated privileges are required. In typical building automation deployments, exposure depends on whether the controller's management interface is reachable from untrusted network segments.
No verified proof-of-concept code is publicly available. Refer to the Siemens Security Advisory SSA-333035 for authoritative technical details.
Detection Methods for CVE-2026-102075
Indicators of Compromise
- Unexpected restarts or crashes of the controller web service on APOGEE or TALON devices
- Loss of web management reachability to controllers without a corresponding operator action
- Inbound HTTP POST requests containing abnormally large or malformed multipart/form-data boundaries targeting controller management interfaces
Detection Strategies
- Deploy network IDS or IPS signatures that flag malformed multipart/form-data requests directed at BACnet or P2 Ethernet controller IP ranges
- Monitor OT network segments for HTTP traffic originating from unexpected IT or external sources toward building automation controllers
- Correlate controller availability telemetry with inbound HTTP request spikes to identify DoS attempts
Monitoring Recommendations
- Enable logging on OT firewalls and jump hosts for all HTTP sessions reaching APOGEE and TALON controllers
- Alert on repeated controller web service restarts within short time windows
- Baseline normal multipart request sizes to the controller web interface and alert on deviations
How to Mitigate CVE-2026-102075
Immediate Actions Required
- Inventory all APOGEE and TALON controllers and identify which variants and firmware versions are deployed
- Restrict network access to controller web services so only authorized engineering workstations can reach them
- Apply vendor-provided firmware updates where available, prioritizing network-exposed devices
Patch Information
Siemens addresses the vulnerability in APOGEE PXC Compact and Modular BACnet V3.5.7 and later, APOGEE PXC Compact and Modular P2 Ethernet V2.8.21 and later, and TALON TC Compact and Modular BACnet V3.5.7 and later. No fix is currently listed for APOGEE MBC (PPC) and APOGEE MEC (PPC) variants. See the Siemens Security Advisory SSA-333035 for authoritative patch details.
Workarounds
- Place controllers behind an OT-aware firewall and permit HTTP management access only from a dedicated engineering VLAN
- Disable the controller web service when it is not required for operations
- Follow Siemens' operational guidelines for industrial security to isolate automation networks from IT and internet-exposed segments
# Example firewall policy restricting controller web access to engineering subnet
# Replace interface, subnets, and controller IPs with site-specific values
iptables -A FORWARD -s 10.20.30.0/24 -d 10.50.0.0/16 -p tcp --dport 80 -j ACCEPT
iptables -A FORWARD -d 10.50.0.0/16 -p tcp --dport 80 -j DROP
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB