CVE-2026-102074: Siemens Building Automation DoS Vulnerability

CVE-2026-102074 is a denial of service vulnerability affecting Siemens building automation systems including APOGEE and TALON controllers. The FTP service flaw allows unauthenticated remote attackers to crash systems. This article covers technical details, affected product versions, security impact, and recommended mitigation strategies.

Published:

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

CVE-2026-102074 Overview

Siemens disclosed CVE-2026-102074, a stack-based buffer overflow [CWE-121] affecting the File Transfer Protocol (FTP) service in multiple APOGEE and TALON building automation controllers. The FTP service fails to validate the length of user-controllable input, allowing an unauthenticated remote attacker to trigger a denial of service against the device. Affected controllers include APOGEE MBC and MEC (PPC) running BACnet or P2 Ethernet firmware, APOGEE PXC Compact and Modular variants, and TALON TC Compact and Modular controllers. These devices are commonly deployed in heating, ventilation, and air conditioning (HVAC) and building management environments.

Critical Impact

An unauthenticated network attacker can crash the FTP service and disrupt availability of building automation controllers that manage HVAC and facility operations.

Affected Products

  • APOGEE MBC (PPC) and MEC (PPC) controllers, both BACnet and P2 Ethernet variants (all versions)
  • APOGEE PXC Compact and PXC Modular controllers: BACnet versions prior to V3.5.7, P2 Ethernet versions prior to V2.8.21
  • TALON TC Compact and TC Modular (BACnet) controllers, all versions prior to V3.5.7

Discovery Timeline

  • 2026-10-13 - CVE-2026-102074 published to the National Vulnerability Database
  • 2026-10-15 - Last updated in NVD database

Technical Details for CVE-2026-102074

Vulnerability Analysis

The flaw resides in the FTP service exposed by the affected APOGEE and TALON controllers. The service accepts input from remote clients without enforcing a maximum length, allowing attacker-supplied data to overflow a fixed-size buffer on the stack. The overflow corrupts stack memory and causes the FTP service or the controller firmware to terminate abnormally. Exploitation requires only network reachability to the FTP port and no authentication or user interaction. Building automation controllers often remain online for long periods and lack automatic restart safeguards, so a successful attack can take control systems offline until manual recovery.

Root Cause

The root cause is improper validation of the length of user-controllable input processed by the FTP command handler, classified as a stack-based buffer overflow [CWE-121]. The vulnerable firmware copies input into a stack buffer without bounds checking, producing deterministic memory corruption when input exceeds the allocated size.

Attack Vector

An unauthenticated attacker with network access to the controller sends a crafted, overly long FTP command or argument to the exposed FTP service. The malformed input overwrites stack memory, crashing the service and interrupting controller operations. The vulnerability is network-exploitable, requires low attack complexity, and impacts availability. Siemens has not reported known in-the-wild exploitation, and no public proof-of-concept is listed in the enriched data. The EPSS probability stands at 0.573%.

See the Siemens Security Advisory SSA-333035 for vendor-specific technical details.

Detection Methods for CVE-2026-102074

Indicators of Compromise

  • Unexpected restarts, watchdog resets, or loss of communication from APOGEE or TALON controllers managing HVAC or facility loads
  • Inbound FTP (TCP/21) connections to controllers from unexpected source addresses, especially outside maintenance windows
  • FTP sessions terminated abruptly after oversized commands or arguments appear in network traffic captures

Detection Strategies

  • Deploy passive operational technology (OT) network monitoring to inspect FTP traffic directed at building automation controllers and alert on malformed or oversized command strings
  • Correlate controller downtime events with FTP connection logs collected from upstream firewalls or OT gateways
  • Use protocol-aware intrusion detection signatures that flag FTP commands exceeding RFC 959 length conventions

Monitoring Recommendations

  • Baseline normal FTP access patterns to each controller and alert on deviations in source IP, frequency, or payload size
  • Forward firewall and OT segment logs to a centralized analytics platform for cross-correlation with controller availability metrics
  • Enable continuous reachability checks against affected controllers so FTP-triggered crashes are detected within minutes

How to Mitigate CVE-2026-102074

Immediate Actions Required

  • Inventory all APOGEE and TALON controllers and identify firmware variants exposing FTP services
  • Block FTP (TCP/21) at the OT perimeter and restrict access to engineering workstations on an isolated management VLAN
  • Apply vendor-updated firmware to PXC Compact, PXC Modular, and TALON TC Compact/Modular (BACnet) controllers as outlined in the Siemens advisory

Patch Information

Siemens has released fixed firmware for a subset of affected products. Upgrade APOGEE PXC Compact and PXC Modular (BACnet) and TALON TC Compact and TC Modular (BACnet) to V3.5.7 or later. Upgrade APOGEE PXC Compact and PXC Modular (P2 Ethernet) to V2.8.21 or later. No fixed version is currently listed for APOGEE MBC (PPC) and MEC (PPC) products; follow mitigations in the Siemens Security Advisory SSA-333035.

Workarounds

  • Disable the FTP service on controllers where it is not operationally required
  • Place affected controllers behind a firewall configured to deny inbound FTP from untrusted networks, following Siemens operational guidelines for industrial security
  • Enforce network segmentation between information technology (IT) and building automation networks, allowing FTP only from a jump host used for firmware management
bash
# Example firewall rule to restrict FTP access to a trusted engineering host
iptables -A FORWARD -p tcp -s 10.20.30.40 -d 10.50.0.0/16 --dport 21 -j ACCEPT
iptables -A FORWARD -p tcp -d 10.50.0.0/16 --dport 21 -j DROP