Skip to main content
CVE Vulnerability Database
Vulnerability Database/CVE-2025-32825

CVE-2025-32825: Siemens Telecontrol Server Basic SQLi Flaw

CVE-2025-32825 is a SQL injection vulnerability in Siemens Telecontrol Server Basic that allows authenticated attackers to bypass authorization and execute code. This article covers technical details, affected versions, and mitigation.

Published:

CVE-2025-32825 Overview

CVE-2025-32825 is a SQL injection vulnerability [CWE-89] affecting Siemens TeleControl Server Basic versions prior to V3.1.2.2. The flaw resides in the internally used GetProjects method, which fails to properly sanitize input before constructing database queries. An authenticated remote attacker with access to TCP port 8000 can bypass authorization controls, read and modify the application database, and execute code under the NT AUTHORITY\NetworkService account. The vulnerability impacts industrial control system (ICS) deployments where TeleControl Server Basic manages remote terminal units (RTUs) over wide-area networks.

Critical Impact

Authenticated attackers can pivot from an authorization bypass to arbitrary database read/write and remote code execution as NetworkService on Siemens TeleControl Server Basic hosts.

Affected Products

  • Siemens TeleControl Server Basic — all versions before V3.1.2.2
  • Deployments exposing TCP port 8000 to the network
  • Industrial environments running TeleControl Server Basic for SCADA/RTU communication

Discovery Timeline

  • 2025-04-16 - CVE-2025-32825 published to NVD
  • 2026-06-17 - Last updated in NVD database

Technical Details for CVE-2025-32825

Vulnerability Analysis

The vulnerability stems from improper neutralization of special elements used in an SQL command within the GetProjects method. This internal routine processes attacker-controlled data and concatenates it directly into a query executed against the application database. Because the affected code path is reachable post-authentication over the network on port 8000, any account with valid credentials becomes a viable attack origin.

Successful exploitation produces three escalating outcomes. First, the injected statements bypass authorization checks enforced at the application layer. Second, the attacker gains read and write access to the underlying database, including project files and configuration tables. Third, the attacker leverages database functionality or stored procedures to execute operating system commands under the NT AUTHORITY\NetworkService identity. From that foothold, lateral movement into the broader operational technology (OT) network becomes feasible.

Root Cause

The GetProjects method constructs SQL queries through string concatenation rather than parameterized statements. Input validation and output encoding are insufficient, allowing meta-characters such as single quotes and statement terminators to alter query semantics. This is a textbook [CWE-89] SQL injection pattern.

Attack Vector

The attack vector is network-based and requires low privileges plus no user interaction. An attacker must reach TCP port 8000 on the host running TeleControl Server Basic and possess authenticated session credentials. From there, crafted requests invoking the GetProjects method deliver the SQL injection payload. Refer to the Siemens Security Advisory SSA-443402 for protocol-level details.

Detection Methods for CVE-2025-32825

Indicators of Compromise

  • Unexpected outbound process execution spawned by the TeleControl Server Basic service running as NT AUTHORITY\NetworkService
  • Database log entries showing malformed or unusually long queries originating from the GetProjects code path
  • New or modified rows in project tables that do not align with operator change-control records
  • Inbound network sessions to TCP port 8000 from non-engineering workstations or unexpected source subnets

Detection Strategies

  • Inspect application and database audit logs for SQL syntax errors, UNION-based queries, or stacked statements referencing GetProjects
  • Alert on child processes launched by the TeleControl Server Basic service binary, particularly cmd.exe, powershell.exe, or scripting interpreters
  • Correlate authentication events on port 8000 with subsequent database write activity to identify abuse of valid credentials

Monitoring Recommendations

  • Forward Windows Security, Sysmon, and application logs from TeleControl Server hosts to a centralized analytics platform for retention and query
  • Baseline normal database query patterns issued by the application service account and alert on deviations
  • Monitor north-south and east-west traffic to port 8000 and restrict it to known engineering management subnets

How to Mitigate CVE-2025-32825

Immediate Actions Required

  • Upgrade Siemens TeleControl Server Basic to version V3.1.2.2 or later as specified in the vendor advisory
  • Restrict network access to TCP port 8000 using host-based firewalls or network ACLs so that only authorized engineering systems can connect
  • Rotate credentials for all accounts permitted to authenticate to the TeleControl Server, particularly service and administrative accounts
  • Audit the application database for unauthorized rows, schema changes, or stored procedure modifications

Patch Information

Siemens has released a fixed version, V3.1.2.2, that addresses CVE-2025-32825. Apply the update following Siemens' deployment guidance in the Siemens Security Advisory SSA-443402. After patching, validate that the GetProjects code path no longer accepts injected SQL by reviewing application logs during regression testing.

Workarounds

  • Place TeleControl Server Basic behind a segmented firewall and permit access to port 8000 only from a hardened jump host
  • Enforce strong, unique credentials and multi-factor authentication on perimeter access paths to reduce the pool of attackers able to authenticate
  • Run the TeleControl Server service with the least privilege necessary and remove unused database accounts or stored procedures that enable command execution
bash
# Example Windows Firewall rule to restrict TCP port 8000 to an engineering subnet
netsh advfirewall firewall add rule name="TeleControl-8000-Restrict" ^
  dir=in action=allow protocol=TCP localport=8000 ^
  remoteip=10.10.20.0/24

netsh advfirewall firewall add rule name="TeleControl-8000-Block-Other" ^
  dir=in action=block protocol=TCP localport=8000

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Default Legacy - Prefooter | Experience the World’s Most Advanced Cybersecurity Platform

Experience the Most Advanced Cybersecurity Platform

See how the world’s most intelligent, autonomous cybersecurity platform can protect your organization today and into the future.