CVE-2026-15953 Overview

CVE-2026-15953 is a path traversal vulnerability [CWE-22] in ABB Protection and control IED manager (PCM600). The flaw affects all versions through 2.14 and stems from improper limitation of a pathname to a restricted directory. An authenticated local attacker who tricks a user into interacting with crafted input can write files outside the intended directory structure. Successful exploitation can compromise the integrity of the PCM600 host and dependent systems used to configure Intelligent Electronic Devices (IEDs) in substation environments.

Critical Impact

Local attackers with low privileges can modify files outside restricted directories, impacting the integrity of PCM600 engineering workstations managing protection relays in electrical substations.

Affected Products

  • ABB Protection and control IED manager (PCM600) — all versions through 2.14
  • Engineering workstations running PCM600 for IED configuration
  • Substation automation environments relying on PCM600 project files

Discovery Timeline

  • 2026-09-28 - CVE CVE-2026-15953 published to NVD
  • 2026-09-28 - Last updated in NVD database

Technical Details for CVE-2026-15953

Vulnerability Analysis

PCM600 is ABB's engineering tool for configuring and managing protection and control IEDs. The vulnerability arises when the application processes file paths supplied through user-influenced input without sufficient canonicalization. An attacker can supply traversal sequences such as ../ to escape the intended working directory. The flaw requires local access, low privileges, and active user interaction, which limits remote exploitation but keeps the risk relevant in multi-user engineering environments.

Root Cause

The root cause is improper limitation of a pathname to a restricted directory [CWE-22]. PCM600 fails to normalize and validate file path components before performing file system operations. Relative path sequences are not stripped or rejected, allowing resolved paths to point outside the application's designated directories. This weakness affects integrity on both the vulnerable component and dependent subsystems.

Attack Vector

Exploitation requires a local attack vector and user interaction. An attacker provides a crafted project file, configuration bundle, or import artifact that PCM600 processes. When the tool extracts or writes referenced files, the traversal sequences redirect writes to arbitrary locations the PCM600 process can access. This can overwrite configuration data, scripts, or binaries used by engineers managing substation IEDs.

No verified public proof-of-concept code is available. See the ABB security advisory for vendor-provided technical details.

Detection Methods for CVE-2026-15953

Indicators of Compromise

  • Unexpected files written outside PCM600 project directories, particularly in system or user profile paths
  • PCM600 project archives or import files containing ..\ or ../ sequences in embedded file references
  • Modification timestamps on PCM600 binaries, templates, or configuration files that do not align with scheduled engineering activity

Detection Strategies

  • Monitor file write activity by the PCM600 process for paths outside its installation and project directories
  • Inspect imported project files and third-party IED configuration bundles for path traversal patterns before processing
  • Correlate user logon sessions on engineering workstations with file system changes to detect anomalous import operations

Monitoring Recommendations

  • Enable file integrity monitoring on PCM600 installation directories and shared project repositories
  • Audit Windows event logs on engineering workstations for unexpected file creation under System32, startup folders, or user profile directories
  • Capture and retain PCM600 application logs for post-incident review of project imports and file operations

How to Mitigate CVE-2026-15953

Immediate Actions Required

  • Restrict access to PCM600 engineering workstations to authorized personnel only and enforce least privilege for interactive logons
  • Only open PCM600 project files and import bundles originating from trusted, verified sources
  • Isolate engineering workstations on dedicated OT management networks separated from corporate IT and the internet

Patch Information

ABB has published a security advisory for this vulnerability. Refer to the ABB security advisory document for fixed version information and official remediation guidance. The vulnerability affects PCM600 versions through 2.14.

Workarounds

  • Validate the contents of PCM600 project files in a sandboxed environment before importing them into production engineering workstations
  • Apply application allowlisting to prevent execution of unauthorized files that may be dropped by traversal exploitation
  • Enforce multi-user review of imported engineering artifacts, particularly those received from external vendors or integrators
bash
# Configuration example
# Example Windows ACL hardening to restrict write access to PCM600 directories
icacls "C:\Program Files (x86)\ABB\PCM600" /inheritance:r
icacls "C:\Program Files (x86)\ABB\PCM600" /grant:r "Administrators:(OI)(CI)F" "SYSTEM:(OI)(CI)F" "Users:(OI)(CI)RX"