Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-15952 Overview
CVE-2026-15952 is an Incorrect Permission Assignment for Critical Resource vulnerability [CWE-732] affecting ABB Protection and control IED manager (PCM600) through version 2.14. PCM600 is engineering software used to configure, commission, and maintain ABB protection and control intelligent electronic devices (IEDs) in substations and industrial power systems. The vulnerability allows a local, authenticated attacker with high privileges to compromise the confidentiality, integrity, and availability of resources protected by file or object permissions. Successful exploitation can let an attacker tamper with configuration files or protection logic that governs electrical equipment operation.
Critical Impact
Weak permissions on PCM600 resources permit a local privileged user to modify engineering data, which in operational technology (OT) environments can affect protection relay behavior and substation safety.
Affected Products
- ABB Protection and control IED manager (PCM600) through version 2.14
Discovery Timeline
- 2026-09-28 - CVE CVE-2026-15952 published to NVD
- 2026-09-28 - Last updated in NVD database
Technical Details for CVE-2026-15952
Vulnerability Analysis
The flaw is categorized as Incorrect Permission Assignment for Critical Resource. PCM600 installs or creates critical resources with permissions that are broader than required for correct operation. A local authenticated user can leverage these permissions to read, modify, or replace resources that should be restricted to administrators or the service account. In an OT engineering workstation, these resources can include IED configuration projects, device templates, logs, and credential-related files.
Exploitation requires local access and existing high privileges on the host, and the attack complexity is rated high because the attacker must satisfy environmental preconditions. There is no user interaction requirement. Impact is confined to the vulnerable component with no scope change to other systems.
At the time of publication, no public proof-of-concept, exploit, or evidence of exploitation in the wild has been reported. The EPSS probability is 0.092%.
Root Cause
The root cause is improper assignment of access control entries on files, directories, registry keys, or similar objects created by PCM600 up to version 2.14. The installer or runtime grants permissions to groups broader than necessary, violating the principle of least privilege described in CWE-732.
Attack Vector
The attack vector is local. An attacker who already holds valid credentials on the engineering workstation can abuse the misconfigured permissions to alter PCM600 artifacts. In practice, this may include substituting IED configuration files staged for download, tampering with project databases, or planting malicious binaries in paths that PCM600 loads during normal operation. See the ABB security advisory PDF for product-specific technical details.
Detection Methods for CVE-2026-15952
Indicators of Compromise
- Unexpected modifications to PCM600 project files, templates, or configuration databases outside scheduled engineering activity.
- New or altered files in PCM600 installation directories owned by non-administrative users.
- IED configuration downloads from PCM600 that do not match the last known-good project baseline.
Detection Strategies
- Audit file and directory ACLs on all PCM600 installation and project paths, flagging write permissions granted to standard users or Everyone.
- Enable Windows object access auditing on PCM600 directories and forward Event IDs 4663 and 4670 to a central log store for review.
- Baseline PCM600 binaries and configuration files with cryptographic hashes and alert on drift.
Monitoring Recommendations
- Monitor engineering workstations for interactive logons by accounts that are not members of the authorized engineering group.
- Correlate PCM600 process activity with file writes to project directories to detect out-of-band modifications.
- Track IED configuration pushes and compare them against change-management tickets.
How to Mitigate CVE-2026-15952
Immediate Actions Required
- Restrict interactive and remote logon to PCM600 engineering workstations to a minimal, named set of engineering personnel.
- Review ACLs on PCM600 installation directories, project folders, and related registry keys, removing write permissions from non-administrative principals.
- Apply the vendor update once available and validate PCM600 project integrity against known-good backups.
Patch Information
ABB has published guidance in the advisory document referenced by NVD. Review the ABB cybersecurity advisory for PCM600 for the fixed version, upgrade procedure, and any required post-upgrade hardening steps. All deployments running PCM600 through version 2.14 should be remediated.
Workarounds
- Place PCM600 engineering workstations on an isolated OT network segment with strict jump-host access controls.
- Enforce application allowlisting on engineering workstations to block execution of unauthorized binaries from PCM600 paths.
- Store master IED configuration projects on access-controlled file shares with versioning, and treat local PCM600 copies as transient.
# Example: tighten NTFS permissions on a PCM600 project directory (Windows)
icacls "C:\\ProgramData\\ABB\\PCM600" /inheritance:r
icacls "C:\\ProgramData\\ABB\\PCM600" /grant:r "Administrators:(OI)(CI)F" "SYSTEM:(OI)(CI)F" "PCM600Engineers:(OI)(CI)M"
icacls "C:\\ProgramData\\ABB\\PCM600" /remove "Users" "Everyone"
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB