Skip to main content
Vulnerability Database/CVE-2024-41796

CVE-2024-41796: Siemens 7KT PAC1260 Authentication Bypass Flaw

CVE-2024-41796 is an authentication bypass vulnerability in Siemens SENTRON 7KT PAC1260 Data Manager that allows password changes without authentication. This article covers the technical details, affected firmware versions, security impact, and recommended mitigation strategies.

Published:

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

CVE-2024-41796 Overview

CVE-2024-41796 affects the Siemens SENTRON 7KT PAC1260 Data Manager across all firmware versions. The web interface allows changing the login password without requiring knowledge of the current password. When chained with the cross-site request forgery (CSRF) vulnerability tracked as CVE-2024-41795, an unauthenticated remote attacker can set the device password to an attacker-controlled value. The flaw is categorized under [CWE-620] Unverified Password Change and impacts the integrity of the device management interface.

Critical Impact

An unauthenticated attacker who tricks an authenticated user into visiting a crafted page can take over the Data Manager account and gain full administrative control of the device.

Affected Products

  • Siemens SENTRON 7KT PAC1260 Data Manager (hardware) — all versions
  • Siemens SENTRON 7KT PAC1260 Data Manager Firmware — all versions
  • Deployments exposing the web management interface to untrusted networks

Discovery Timeline

  • 2025-04-08 - CVE-2024-41796 published to the National Vulnerability Database
  • 2026-06-17 - Last updated in the NVD database

Technical Details for CVE-2024-41796

Vulnerability Analysis

The SENTRON 7KT PAC1260 Data Manager is a web-managed energy monitoring gateway. Its password change workflow does not require submission or verification of the current password. Any authenticated session that reaches the password change endpoint can rewrite credentials directly.

The missing re-authentication control becomes exploitable at scale when paired with CVE-2024-41795, a CSRF weakness in the same interface. An attacker only needs an authenticated administrator to load a malicious page in a browser that holds a valid session cookie for the device.

Root Cause

The root cause is an unverified password change, classified as [CWE-620]. The web application accepts a new password without requiring the user to prove knowledge of the existing one. This violates standard account management controls that enforce reauthentication for sensitive state changes.

Attack Vector

Exploitation requires network reachability to the device web interface and user interaction from an authenticated operator. The attacker hosts a crafted HTML page or link that issues a forged password-change request to the Data Manager. The browser attaches the operator's session, the server accepts the request without verifying the current password, and credentials are overwritten. The attacker then logs in with the chosen value and controls the device.

No verified public exploit code or proof-of-concept has been published. Technical details are described in prose only; see the Siemens Security Advisory SSA-187636 for vendor guidance.

Detect Identity Attacks the Moment Authentication Fails

Singularity™ Identity surfaces credential misuse, lateral movement, and privilege escalation in real time, so you can contain the breach before it spreads.

Stop Identity Attacks

Detection Methods for CVE-2024-41796

Indicators of Compromise

  • Unexpected password changes on SENTRON 7KT PAC1260 Data Manager accounts without a prior reset request from an administrator.
  • Successful logins from unfamiliar source IP addresses immediately following a password change event.
  • HTTP POST requests to the password change endpoint originating from external referrers or cross-origin sources.

Detection Strategies

  • Inspect web server and proxy logs in front of the Data Manager for password change requests that lack a prior authenticated password reset workflow.
  • Alert on HTTP requests to the device management interface that carry a Referer or Origin header pointing to a domain outside the operational network.
  • Correlate password change events with subsequent configuration modifications on the same device within short time windows.

Monitoring Recommendations

  • Enable verbose audit logging on the Data Manager and forward events to a centralized SIEM or data lake for retention and correlation.
  • Monitor north-south traffic to operational technology (OT) segments for unexpected HTTP sessions reaching device management ports.
  • Baseline the normal set of workstations that administer the device and alert when management traffic arrives from any other source.

How to Mitigate CVE-2024-41796

Immediate Actions Required

  • Restrict network access to the SENTRON 7KT PAC1260 Data Manager web interface to a dedicated management VLAN or jump host.
  • Require administrators to log out of the Data Manager interface before browsing untrusted sites or email in the same browser session.
  • Review all local accounts on affected devices and rotate credentials if any unauthorized change is suspected.

Patch Information

Siemens has not published a fixed firmware version for CVE-2024-41796 in the referenced advisory. Review the Siemens Security Advisory SSA-187636 for the current remediation status and apply any updates as soon as they are released.

Workarounds

  • Place the device behind a firewall that permits management access only from trusted administrator workstations.
  • Disable or block external access to the device web interface where the product is reachable from business or internet-facing networks.
  • Use a dedicated, hardened browser profile for OT device administration to reduce CSRF exposure from general browsing.
  • Follow Siemens operational guidelines for industrial security and the defense-in-depth recommendations referenced in the vendor advisory.
bash
# Example firewall rule restricting Data Manager web access to a management subnet
# Replace interface and subnet values with your environment specifics
iptables -A INPUT -p tcp --dport 80 -s 10.10.50.0/24 -d <device_ip> -j ACCEPT
iptables -A INPUT -p tcp --dport 80 -d <device_ip> -j DROP
iptables -A INPUT -p tcp --dport 443 -s 10.10.50.0/24 -d <device_ip> -j ACCEPT
iptables -A INPUT -p tcp --dport 443 -d <device_ip> -j DROP

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

Experience the Most Advanced Cybersecurity Platform

See how the world’s most intelligent, autonomous cybersecurity platform can protect your organization today and into the future.