CVE-2024-41791 Overview
CVE-2024-41791 affects the Siemens SENTRON 7KT PAC1260 Data Manager across all firmware versions. The web interface fails to authenticate report creation requests. An unauthenticated remote attacker with network access to the device can read or clear log files, reset the device, or change the system date and time. The flaw is categorized under [CWE-306] Missing Authentication for Critical Function. Siemens published advisory SSA-187636 to track the issue.
Critical Impact
Unauthenticated network attackers can tamper with device logs, disrupt operation through resets, and manipulate system time on energy monitoring equipment.
Affected Products
- Siemens SENTRON 7KT PAC1260 Data Manager (all hardware revisions)
- Siemens SENTRON 7KT PAC1260 Data Manager Firmware (all versions)
- Deployments using the built-in web interface for report generation
Discovery Timeline
- 2025-04-08 - CVE-2024-41791 published to the National Vulnerability Database
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2024-41791
Vulnerability Analysis
The SENTRON 7KT PAC1260 Data Manager exposes a web interface used for configuration and report generation. The report creation endpoints do not verify caller identity before executing requested actions. Attackers reach these endpoints over the network without credentials, cookies, or tokens.
The endpoints handle more than report generation. They also accept commands that read log files, clear log files, reset the device, and set date and time. The absence of authentication turns administrative functions into anonymous operations.
Because the device performs energy monitoring, log manipulation erases forensic evidence of tampering. Time changes distort measurement records tied to billing or grid analytics. Device resets interrupt data collection cycles.
Root Cause
The root cause is a missing authentication check on report creation handlers within the web interface, tracked as [CWE-306]. The application logic assumes requests reaching these endpoints are authorized, without validating a session or credential. No compensating access control enforces least privilege at the network layer by default.
Attack Vector
Exploitation requires network reachability to the device web interface, low attack complexity, no privileges, and no user interaction. An attacker sends crafted HTTP requests to the vulnerable report endpoints and receives responses or triggers side effects. Devices exposed to shared operational technology (OT) networks or, worse, to the internet are directly reachable. The vulnerability does not require chaining with other flaws.
No verified public proof-of-concept code is available. Refer to the Siemens Security Advisory SSA-187636 for vendor technical details.
Detection Methods for CVE-2024-41791
Indicators of Compromise
- Unexpected gaps or truncation in device log files without a corresponding administrative action
- Sudden device reboots recorded in upstream SCADA or monitoring systems
- System clock drift or abrupt time changes on the 7KT PAC1260 that do not match NTP synchronization events
- HTTP requests to report creation URLs from unrecognized source addresses
Detection Strategies
- Inspect HTTP access logs on the device or upstream proxies for anonymous requests targeting report and administrative endpoints
- Correlate device reset events with authenticated administrative sessions; unattributed resets indicate abuse
- Monitor for log clearing events that occur outside scheduled maintenance windows
Monitoring Recommendations
- Forward device event logs and syslog streams to a centralized SIEM for tamper-evident storage
- Alert on time synchronization deltas exceeding a defined threshold on OT metering devices
- Track HTTP request patterns to the 7KT PAC1260 web interface and baseline expected administrative sources
How to Mitigate CVE-2024-41791
Immediate Actions Required
- Restrict network access to the 7KT PAC1260 web interface to trusted management hosts using firewall or VLAN segmentation
- Remove the device from any internet-facing exposure and verify with external scanning
- Review device logs and configuration for evidence of unauthorized resets, log clearing, or time changes
- Consult Siemens Security Advisory SSA-187636 for the latest vendor guidance
Patch Information
Siemens has published advisory SSA-187636 covering CVE-2024-41791. Consult the advisory for the current fix status and any recommended firmware update for the SENTRON 7KT PAC1260 Data Manager. Apply vendor-supplied updates through standard OT change management processes.
Workarounds
- Place the device behind a network access control layer that permits only authenticated engineering workstations to reach the web interface
- Disable or block external access to report creation URLs at the perimeter until a firmware fix is deployed
- Follow Siemens operational guidelines for securing industrial control systems, including defense-in-depth network segmentation
# Example firewall restriction limiting web interface access to a trusted management subnet
iptables -A FORWARD -p tcp -s 10.20.30.0/24 -d <device_ip> --dport 80 -j ACCEPT
iptables -A FORWARD -p tcp -d <device_ip> --dport 80 -j DROP