Skip to main content
CVE Vulnerability Database
Vulnerability Database/CVE-2024-41791

CVE-2024-41791: Siemens 7KT PAC1260 Auth Bypass Flaw

CVE-2024-41791 is an authentication bypass vulnerability in Siemens SENTRON 7KT PAC1260 Data Manager that allows unauthenticated attackers to manipulate logs and device settings. This article covers technical details, affected versions, security impact, and mitigation strategies.

Published:

CVE-2024-41791 Overview

CVE-2024-41791 affects the Siemens SENTRON 7KT PAC1260 Data Manager across all firmware versions. The web interface fails to authenticate report creation requests. An unauthenticated remote attacker with network access to the device can read or clear log files, reset the device, or change the system date and time. The flaw is categorized under [CWE-306] Missing Authentication for Critical Function. Siemens published advisory SSA-187636 to track the issue.

Critical Impact

Unauthenticated network attackers can tamper with device logs, disrupt operation through resets, and manipulate system time on energy monitoring equipment.

Affected Products

  • Siemens SENTRON 7KT PAC1260 Data Manager (all hardware revisions)
  • Siemens SENTRON 7KT PAC1260 Data Manager Firmware (all versions)
  • Deployments using the built-in web interface for report generation

Discovery Timeline

  • 2025-04-08 - CVE-2024-41791 published to the National Vulnerability Database
  • 2026-06-17 - Last updated in NVD database

Technical Details for CVE-2024-41791

Vulnerability Analysis

The SENTRON 7KT PAC1260 Data Manager exposes a web interface used for configuration and report generation. The report creation endpoints do not verify caller identity before executing requested actions. Attackers reach these endpoints over the network without credentials, cookies, or tokens.

The endpoints handle more than report generation. They also accept commands that read log files, clear log files, reset the device, and set date and time. The absence of authentication turns administrative functions into anonymous operations.

Because the device performs energy monitoring, log manipulation erases forensic evidence of tampering. Time changes distort measurement records tied to billing or grid analytics. Device resets interrupt data collection cycles.

Root Cause

The root cause is a missing authentication check on report creation handlers within the web interface, tracked as [CWE-306]. The application logic assumes requests reaching these endpoints are authorized, without validating a session or credential. No compensating access control enforces least privilege at the network layer by default.

Attack Vector

Exploitation requires network reachability to the device web interface, low attack complexity, no privileges, and no user interaction. An attacker sends crafted HTTP requests to the vulnerable report endpoints and receives responses or triggers side effects. Devices exposed to shared operational technology (OT) networks or, worse, to the internet are directly reachable. The vulnerability does not require chaining with other flaws.

No verified public proof-of-concept code is available. Refer to the Siemens Security Advisory SSA-187636 for vendor technical details.

Detection Methods for CVE-2024-41791

Indicators of Compromise

  • Unexpected gaps or truncation in device log files without a corresponding administrative action
  • Sudden device reboots recorded in upstream SCADA or monitoring systems
  • System clock drift or abrupt time changes on the 7KT PAC1260 that do not match NTP synchronization events
  • HTTP requests to report creation URLs from unrecognized source addresses

Detection Strategies

  • Inspect HTTP access logs on the device or upstream proxies for anonymous requests targeting report and administrative endpoints
  • Correlate device reset events with authenticated administrative sessions; unattributed resets indicate abuse
  • Monitor for log clearing events that occur outside scheduled maintenance windows

Monitoring Recommendations

  • Forward device event logs and syslog streams to a centralized SIEM for tamper-evident storage
  • Alert on time synchronization deltas exceeding a defined threshold on OT metering devices
  • Track HTTP request patterns to the 7KT PAC1260 web interface and baseline expected administrative sources

How to Mitigate CVE-2024-41791

Immediate Actions Required

  • Restrict network access to the 7KT PAC1260 web interface to trusted management hosts using firewall or VLAN segmentation
  • Remove the device from any internet-facing exposure and verify with external scanning
  • Review device logs and configuration for evidence of unauthorized resets, log clearing, or time changes
  • Consult Siemens Security Advisory SSA-187636 for the latest vendor guidance

Patch Information

Siemens has published advisory SSA-187636 covering CVE-2024-41791. Consult the advisory for the current fix status and any recommended firmware update for the SENTRON 7KT PAC1260 Data Manager. Apply vendor-supplied updates through standard OT change management processes.

Workarounds

  • Place the device behind a network access control layer that permits only authenticated engineering workstations to reach the web interface
  • Disable or block external access to report creation URLs at the perimeter until a firmware fix is deployed
  • Follow Siemens operational guidelines for securing industrial control systems, including defense-in-depth network segmentation
bash
# Example firewall restriction limiting web interface access to a trusted management subnet
iptables -A FORWARD -p tcp -s 10.20.30.0/24 -d <device_ip> --dport 80 -j ACCEPT
iptables -A FORWARD -p tcp -d <device_ip> --dport 80 -j DROP

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Default Legacy - Prefooter | Experience the World’s Most Advanced Cybersecurity Platform

Experience the Most Advanced Cybersecurity Platform

See how the world’s most intelligent, autonomous cybersecurity platform can protect your organization today and into the future.