Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-45452 Overview
CVE-2026-45452 is a format string vulnerability [CWE-134] affecting Unitronics UniStream Pro programmable logic controllers (PLCs) running UniLogic firmware. The flaw allows an authenticated remote attacker to supply externally-controlled format specifiers to a vulnerable processing routine. Successful exploitation can lead to memory disclosure, memory corruption, and control over execution flow on the affected industrial controller.
The vulnerability was published by the Israeli Government CVE coordination program and affects UniStream Pro B10 and C10 models running UniLogic firmware prior to version 1.41.329.
Critical Impact
An authenticated network attacker can leverage format specifier injection to disclose process memory, corrupt controller state, or disrupt operations on industrial PLCs managing physical processes.
Affected Products
- Unitronics UniStream Pro B10 (UniLogic versions prior to 1.41.329)
- Unitronics UniStream Pro C10 (UniLogic versions prior to 1.41.329)
- UniLogic programming environment integrated with the affected UniStream Pro controllers
Discovery Timeline
- 2026-10-15 - CVE-2026-45452 published to NVD
- 2026-10-16 - Last updated in NVD database
Technical Details for CVE-2026-45452
Vulnerability Analysis
The vulnerability is a classic Use of Externally-Controlled Format String weakness [CWE-134]. The UniLogic runtime on UniStream Pro controllers passes attacker-influenced input directly into a formatted output function without sanitization. Format specifiers such as %s, %x, or %n embedded in the attacker-controlled string are then interpreted by the formatter.
Because the attack vector is network-based and only low-privileged authentication is required, any legitimate operator or compromised account on the controller's management interface can trigger the condition. The impact includes high confidentiality loss through arbitrary memory reads, high integrity loss through arbitrary memory writes using %n-style specifiers, and limited availability impact through forced crashes.
Root Cause
The root cause is improper neutralization of input before it is used as a format string argument. User-supplied data reaches a printf-family routine as the format parameter rather than as a variadic argument. UniLogic firmware releases prior to 1.41.329 do not validate or escape format specifiers in the affected code path.
Attack Vector
An authenticated attacker on a network path to the UniStream Pro controller submits a crafted request containing format specifier metacharacters. The vulnerable handler forwards the string to a formatting function, causing the specifiers to be processed against the current stack frame. Read-oriented specifiers expose memory contents, while %n write primitives can corrupt controller state or redirect execution.
In operational technology (OT) environments, exploitation can affect ladder logic execution, HMI integrity, and the physical processes the PLC controls. See the Israeli Government CVE Advisories for coordinator-published technical details.
Detection Methods for CVE-2026-45452
Indicators of Compromise
- Inbound requests to UniStream Pro management or communication services containing format specifier sequences such as %s, %x, %p, or %n.
- Unexpected UniLogic runtime crashes, restarts, or watchdog resets on B10 or C10 controllers.
- Anomalous reads of PLC memory regions or unexpected changes to ladder logic variables and tags.
- Authentication events from unexpected source addresses to UniStream Pro controllers.
Detection Strategies
- Deploy OT-aware network monitoring to inspect Unitronics PCOM and related protocols for format specifier patterns in user-controlled fields.
- Correlate authentication logs from UniStream Pro controllers with session-level requests to identify low-privileged accounts probing input fields.
- Baseline normal UniLogic firmware behavior and alert on process restarts, abnormal CPU usage, or unexpected diagnostic output.
Monitoring Recommendations
- Forward UniStream Pro diagnostic logs and syslog data to a centralized SIEM for retention and correlation.
- Monitor north-south and east-west traffic between engineering workstations and PLCs for anomalous command sequences.
- Track firmware version inventory to confirm all UniStream Pro B10 and C10 devices are running 1.41.329 or later.
How to Mitigate CVE-2026-45452
Immediate Actions Required
- Upgrade all Unitronics UniStream Pro B10 and C10 controllers to UniLogic version 1.41.329 or later.
- Restrict network access to UniStream Pro management interfaces to authorized engineering workstations only.
- Rotate credentials used to authenticate to UniStream Pro controllers, especially any shared or low-privileged accounts.
- Audit controller access logs for suspicious authentication or request patterns since the affected firmware was deployed.
Patch Information
Unitronics addresses CVE-2026-45452 in UniLogic version 1.41.329. Operators of UniStream Pro B10 and C10 hardware must install this release or newer. Refer to the Israeli Government CVE Advisories listing for coordinator guidance and vendor references.
Workarounds
- Place UniStream Pro controllers behind a firewall or OT-specific gateway that permits only allow-listed engineering hosts.
- Segment PLC networks from corporate IT networks and remove direct internet exposure to Unitronics devices.
- Enforce strong, unique credentials and disable unused accounts on affected controllers until patching is complete.
- Enable protocol-level inspection on OT firewalls to drop requests containing suspicious format specifier characters.
# Example firewall rule to restrict access to UniStream Pro management port
# Allow only engineering workstation subnet to reach the controller
iptables -A FORWARD -s 10.10.20.0/24 -d 10.50.1.10 -p tcp --dport 20256 -j ACCEPT
iptables -A FORWARD -d 10.50.1.10 -p tcp --dport 20256 -j DROP