Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-27874 Overview
CVE-2026-27874 is a hard-coded credentials vulnerability affecting Johnson Controls EasyIO FS32 building automation controllers. The flaw falls under [CWE-798: Use of Hard-coded Credentials]. An attacker with low privileges and adjacent network access can exploit embedded credentials to disrupt availability on the device. The vulnerability affects all EasyIO FS32 firmware versions prior to 3.0b63.
Critical Impact
Adjacent-network attackers who recover the hard-coded credentials can authenticate to EasyIO FS32 controllers and trigger a high-impact availability loss, potentially interrupting building automation processes.
Affected Products
- Johnson Controls EasyIO FS32 firmware prior to 3.0b63
Discovery Timeline
- 2026-10-01 - CVE-2026-27874 published to NVD
- 2026-10-02 - Last updated in NVD database
Technical Details for CVE-2026-27874
Vulnerability Analysis
The EasyIO FS32 controller ships with hard-coded credentials embedded in firmware. These credentials are identical across deployed units, so recovery from one device discloses access to every installation running an affected build. The CWE-798 classification confirms that the authentication secret is stored within the product itself rather than provisioned per device.
Successful authentication using the embedded credentials grants control over availability-impacting functionality on the controller. The CVSS vector indicates no confidentiality or integrity impact, but availability loss is high. Because EasyIO FS32 devices control heating, ventilation, and building automation workloads, a loss of availability can translate into operational disruption for the facility.
The attack is bounded to adjacent network access, meaning an attacker must reach the controller's management network segment rather than attack it directly from the public internet. Flat operational technology (OT) networks and poorly segmented building automation VLANs materially increase exposure.
Root Cause
The root cause is the inclusion of static credentials in the firmware image. Johnson Controls remediated the condition in EasyIO FS32 build 3.0b63, which removes the hard-coded authentication path.
Attack Vector
An attacker on an adjacent network segment extracts the credentials from firmware or public artifacts, authenticates to the controller, and issues commands that degrade or disable the device. User interaction is not required. No proof-of-concept exploit is currently published, and the issue is not listed in the CISA Known Exploited Vulnerabilities catalog.
No verified exploit code is published for this issue. Refer to the Johnson Controls Security Advisory for vendor-authored technical details.
Detect Identity Attacks the Moment Authentication Fails
Singularity™ Identity surfaces credential misuse, lateral movement, and privilege escalation in real time, so you can contain the breach before it spreads.
Stop Identity AttacksDetection Methods for CVE-2026-27874
Indicators of Compromise
- Successful authentication events to EasyIO FS32 management interfaces from hosts that are not part of the sanctioned engineering workstation inventory.
- Unexpected controller reboots, configuration resets, or service outages affecting building automation points on FS32 devices.
- New or unusual TCP sessions to the FS32 web and control ports originating from adjacent OT or IT subnets.
Detection Strategies
- Inventory all EasyIO FS32 devices and compare firmware versions against the fixed build 3.0b63 to identify vulnerable units.
- Monitor north-south and east-west traffic to building automation controllers for authentication attempts from unauthorized hosts.
- Alert on configuration changes or firmware operations initiated outside scheduled maintenance windows.
Monitoring Recommendations
- Forward FS32 authentication, configuration, and system logs to a centralized logging platform for correlation.
- Baseline normal control-system traffic and alert on deviations such as new source IPs reaching management interfaces.
- Review passive OT discovery data (for example from span ports or OT sensors) for FS32 banners exposing vulnerable firmware builds.
How to Mitigate CVE-2026-27874
Immediate Actions Required
- Upgrade EasyIO FS32 controllers to firmware 3.0b63 or later as published in the Johnson Controls advisory.
- Restrict network reachability of FS32 management interfaces to a dedicated, segmented engineering VLAN.
- Rotate any credentials and keys that may have been exposed by the hard-coded authentication path once firmware is updated.
Patch Information
Johnson Controls addresses the hard-coded credentials condition in EasyIO FS32 build 3.0b63. Consult the Johnson Controls Security Advisory for firmware packages and installation guidance.
Workarounds
- Place FS32 controllers behind a firewall that only permits traffic from authorized building automation workstations.
- Disable or block remote management services on FS32 devices where operationally feasible until patching completes.
- Require VPN plus multi-factor authentication for any remote engineering access to the OT segment hosting FS32 controllers.
# Example: restrict access to FS32 management interface to an engineering host
# Replace FS32_IP and ENG_WORKSTATION_IP with site-specific values
iptables -A FORWARD -s ENG_WORKSTATION_IP -d FS32_IP -p tcp --dport 80 -j ACCEPT
iptables -A FORWARD -d FS32_IP -p tcp --dport 80 -j DROP
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB