Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-27873 Overview
CVE-2026-27873 is a hard-coded credentials vulnerability [CWE-798] in Johnson Controls EasyIO FG controllers. The flaw allows an authenticated local attacker to perform password spraying against embedded credentials shipped with the device firmware. Successful exploitation can compromise the confidentiality, integrity, and availability of the controller and connected subsystems. Johnson Controls has addressed the issue in EasyIO FG version 2.0b52.
Critical Impact
Attackers with local access can leverage embedded credentials to gain control over building automation functions managed by EasyIO FG controllers.
Affected Products
- Johnson Controls EasyIO FG, all versions prior to 2.0b52
Discovery Timeline
- 2026-10-01 - CVE-2026-27873 published to NVD
- 2026-10-02 - Last updated in NVD database
Technical Details for CVE-2026-27873
Vulnerability Analysis
The vulnerability stems from hard-coded credentials embedded within the EasyIO FG firmware. These credentials remain constant across deployments and cannot be rotated through normal administrative workflows. An attacker who extracts or discovers the credentials can authenticate to any unpatched EasyIO FG controller without defeating standard authentication mechanisms.
Because the credentials are reusable across installations, a single disclosure enables password spraying across every vulnerable device the attacker can reach. The CWE-798 classification identifies the underlying weakness: credentials stored in a form that is accessible to anyone with sufficient access to the binary or runtime environment.
Successful authentication grants access to building automation functions managed by the controller, which may include HVAC, lighting, and sensor subsystems. Impact extends beyond the device itself to connected systems that trust the controller.
Root Cause
The root cause is the inclusion of static credentials inside the EasyIO FG firmware distribution. The device accepts those credentials for authentication, bypassing per-deployment account provisioning.
Attack Vector
Exploitation requires local access and low privileges, with high attack complexity because an attacker must first obtain or guess the embedded secret. Once credentials are known, authentication succeeds without user interaction. Attackers reuse the same credentials across controllers in a password spraying pattern.
No verified public exploit code is available. Technical details are published in the Johnson Controls Security Advisories.
Detect Identity Attacks the Moment Authentication Fails
Singularity™ Identity surfaces credential misuse, lateral movement, and privilege escalation in real time, so you can contain the breach before it spreads.
Stop Identity AttacksDetection Methods for CVE-2026-27873
Indicators of Compromise
- Authentication events on EasyIO FG controllers originating from unexpected hosts or service accounts.
- Repeated login attempts across multiple controllers using identical credentials, consistent with password spraying.
- Configuration changes on EasyIO FG devices outside maintenance windows.
Detection Strategies
- Inventory EasyIO FG controllers and compare firmware versions against the fixed release 2.0b52.
- Correlate controller authentication logs with user directories to flag logins that do not match provisioned operator accounts.
- Baseline normal operator source addresses and alert on deviations.
Monitoring Recommendations
- Forward controller and building management system logs to a centralized SIEM for retention and correlation.
- Monitor network segments hosting EasyIO FG devices for unexpected management traffic on controller administration ports.
- Alert on bulk authentication activity targeting multiple controllers in short time windows.
How to Mitigate CVE-2026-27873
Immediate Actions Required
- Upgrade all Johnson Controls EasyIO FG controllers to version 2.0b52 or later.
- Restrict network access to EasyIO FG management interfaces to trusted engineering workstations only.
- Audit controller accounts and remove any sessions established before patching.
Patch Information
Johnson Controls has released EasyIO FG firmware 2.0b52 to remediate CVE-2026-27873. Refer to the Johnson Controls Security Advisories portal for the official advisory and firmware download instructions.
Workarounds
- Place EasyIO FG controllers behind a dedicated operational technology (OT) firewall with strict access control lists.
- Disable or isolate controller management interfaces from general enterprise and internet-facing networks.
- Enforce jump host access to building automation networks and log all administrative sessions.
# Example firewall policy restricting EasyIO FG management access
# Replace addresses with values appropriate for the environment
iptables -A INPUT -p tcp -s 10.10.20.0/24 --dport 80 -j ACCEPT
iptables -A INPUT -p tcp -s 10.10.20.0/24 --dport 443 -j ACCEPT
iptables -A INPUT -p tcp --dport 80 -j DROP
iptables -A INPUT -p tcp --dport 443 -j DROP
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB