CVE-2026-24790 Overview
CVE-2026-24790 is a Missing Authentication vulnerability affecting industrial Programmable Logic Controller (PLC) devices. The underlying PLC of the device can be remotely influenced without proper safeguards or authentication, allowing unauthenticated attackers to manipulate critical industrial control system components over the network.
Critical Impact
Remote attackers can manipulate PLC operations without authentication, potentially disrupting industrial processes, modifying control logic, or causing operational safety hazards in critical infrastructure environments.
Affected Products
- Welker Industrial PLC Devices (specific versions not disclosed)
- Devices referenced in CISA ICS Advisory ICSA-26-050-04
Discovery Timeline
- 2026-02-20 - CVE-2026-24790 published to NVD
- 2026-02-20 - Last updated in NVD database
Technical Details for CVE-2026-24790
Vulnerability Analysis
This vulnerability is classified as CWE-306: Missing Authentication for Critical Function. The affected PLC devices lack proper authentication mechanisms for network-accessible interfaces, allowing remote attackers to interact with the PLC without providing valid credentials. This architectural flaw enables unauthorized manipulation of industrial control systems across the network.
The network-accessible nature of this vulnerability means attackers can reach vulnerable devices from remote locations without requiring local access or user interaction. The impact primarily affects the integrity of the system, allowing unauthorized modifications to PLC operations, with secondary availability implications that could disrupt normal industrial processes.
Root Cause
The root cause of CVE-2026-24790 is the absence of authentication controls on the PLC's network interface. Industrial control systems often prioritize operational continuity and ease of access, which can lead to insufficient security controls being implemented. In this case, the PLC accepts commands and configuration changes from any network-connected client without verifying identity or authorization.
Attack Vector
The attack vector is network-based, requiring no authentication, no user interaction, and low complexity to exploit. An attacker with network access to the vulnerable PLC can directly send commands to manipulate the device's operation. This could include:
- Modifying PLC ladder logic or control programs
- Altering setpoints and operational parameters
- Disrupting process control sequences
- Reading sensitive configuration data
- Stopping or starting PLC operations
The vulnerability is particularly concerning in industrial environments where PLCs control physical processes, as unauthorized manipulation could lead to equipment damage, production disruptions, or safety incidents.
Detection Methods for CVE-2026-24790
Indicators of Compromise
- Unexpected network connections to PLC management interfaces from unauthorized IP addresses
- Configuration changes to PLC logic or parameters without corresponding authorized change tickets
- Anomalous command sequences sent to PLC devices outside normal operational patterns
- Network traffic to PLC ports from external or untrusted network segments
Detection Strategies
- Deploy network intrusion detection systems (NIDS) with ICS/SCADA protocol awareness to monitor traffic to PLC devices
- Implement network segmentation monitoring to detect unauthorized access attempts to OT networks
- Enable logging on all network infrastructure devices to capture connection attempts to PLC management interfaces
- Use industrial protocol deep packet inspection to identify anomalous or unauthorized PLC commands
Monitoring Recommendations
- Establish baseline network traffic patterns for PLC communications and alert on deviations
- Monitor for configuration changes on PLC devices using change detection mechanisms
- Implement real-time alerting for any connections to PLC devices from non-whitelisted sources
- Review access logs regularly for unauthorized access attempts to industrial control systems
How to Mitigate CVE-2026-24790
Immediate Actions Required
- Isolate affected PLC devices from untrusted networks immediately using network segmentation
- Implement firewall rules to restrict access to PLC management interfaces to authorized IP addresses only
- Contact Welker support for vendor-specific guidance and patches
- Review the CISA ICS Advisory ICSA-26-050-04 for official mitigation guidance
Patch Information
No specific patch information is currently available in the CVE data. Organizations should monitor the CISA ICS Advisory and vendor communications for firmware updates that address this authentication bypass vulnerability. The GitHub CSAF documentation may contain additional technical details and remediation guidance.
Workarounds
- Implement network segmentation to isolate PLC devices on dedicated OT/ICS network segments
- Deploy a VPN or jump server architecture requiring authentication before accessing PLC networks
- Configure firewall rules to allow only specific, authorized systems to communicate with PLCs
- Implement network access control (NAC) to prevent unauthorized devices from connecting to OT networks
- Consider deploying an industrial demilitarized zone (IDMZ) architecture between IT and OT networks
# Example firewall rule to restrict PLC access (adapt to your environment)
# Allow only authorized engineering workstation to access PLC
iptables -A INPUT -s 192.168.100.10 -d 192.168.200.50 -p tcp --dport 502 -j ACCEPT
iptables -A INPUT -d 192.168.200.50 -p tcp --dport 502 -j DROP
# Log all connection attempts to PLC networks for monitoring
iptables -A INPUT -d 192.168.200.0/24 -j LOG --log-prefix "PLC_ACCESS: "
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.