Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2026-16438 Overview
CVE-2026-16438 is an Incorrect Privilege Assignment vulnerability [CWE-266] affecting Mitsubishi Electric GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, and MC Works64 products. The installers unnecessarily grant default Distributed Component Object Model (DCOM) permissions to the administrator account of the affected products. An attacker able to log in with that administrator account can launch and operate DCOM objects locally or remotely without the User Account Control (UAC) elevation these operations should require. Successful exploitation can lead to information disclosure, data tampering, data destruction, or a denial-of-service (DoS) condition on the affected system.
Critical Impact
An authenticated administrator can bypass UAC elevation to execute privileged DCOM operations locally or remotely, enabling full compromise of confidentiality, integrity, and availability.
Affected Products
- Mitsubishi Electric GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI versions 10.97.3 and prior
- Mitsubishi Electric MC Works64 (all versions)
- Mitsubishi Electric Iconics Digital Solutions GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI versions 10.97.3 and prior
Discovery Timeline
- 2026-10-15 - CVE-2026-16438 published to the National Vulnerability Database (NVD)
- 2026-10-16 - CVE-2026-16438 last updated in the NVD database
Technical Details for CVE-2026-16438
Vulnerability Analysis
The vulnerability resides in the installation routines of the affected ICONICS and Mitsubishi Electric products. During installation, the installers assign broad default DCOM launch and activation permissions to the product administrator account. These permissions permit DCOM object instantiation and invocation without triggering a UAC elevation prompt.
DCOM is the Windows mechanism that lets software components communicate across process and host boundaries. Operations that normally require integrity-level elevation can be invoked directly by any account holding the misassigned DCOM permissions. In industrial environments, GENESIS64 and ICONICS Suite often orchestrate human-machine interface (HMI) and historian functions, so unauthorized DCOM activation can reach supervisory control logic.
Root Cause
The root cause is improper privilege assignment during product installation. The installer applies DCOM Access Control Lists (ACLs) that treat the product administrator account as fully trusted for remote and local activation. No supplementary UAC elevation check is enforced on sensitive DCOM objects, so the Windows integrity model intended to protect privileged operations is effectively bypassed.
Attack Vector
Exploitation requires an attacker to authenticate using the same administrator account configured for the affected products. Once authenticated, the attacker can call DCOM endpoints locally or over the network to launch and operate objects that would normally demand elevated consent. The adversary can then read, modify, or delete internal product information, or push the affected system into a DoS state. The vulnerability is tracked in Mitsubishi Electric Vulnerability Advisory 2026-006.
Detection Methods for CVE-2026-16438
Indicators of Compromise
- Unexpected DCOM activation events in the Windows Event Log (Event IDs 10000-10038) referencing GENESIS64, ICONICS, or Hyper Historian CLSIDs
- Remote DCOM invocations originating from hosts that do not normally interact with the HMI or historian servers
- Administrator-account logons from unusual source workstations or outside maintenance windows
Detection Strategies
- Audit DCOM ACLs on affected hosts and compare launch, activation, and access permissions against a hardened baseline
- Correlate Security log events 4624 (logon) and 4672 (special privileges assigned) for the product administrator account with subsequent DCOM activity
- Hunt for process creation events where svchost.exe -k DcomLaunch spawns ICONICS or Mitsubishi Electric binaries following remote authentication
Monitoring Recommendations
- Enable DCOM auditing through Group Policy and forward events to a centralized SIEM for correlation
- Monitor RPC endpoint mapper traffic (TCP 135) and ephemeral DCOM ports between operational technology (OT) and information technology (IT) network segments
- Alert on configuration or project file modifications on GENESIS64 and Hyper Historian servers outside approved change windows
How to Mitigate CVE-2026-16438
Immediate Actions Required
- Restrict interactive and network logon rights for the product administrator account to a limited set of trusted operators and management hosts
- Review and tighten DCOM launch, activation, and access permissions using dcomcnfg to remove excessive grants to the administrator account
- Place affected GENESIS64, ICONICS Suite, Hyper Historian, AnalytiX, MobileHMI, and MC Works64 systems behind network segmentation and block TCP 135 and DCOM ports from untrusted networks
Patch Information
Mitsubishi Electric and ICONICS have published guidance in Mitsubishi Electric Vulnerability Advisory 2026-006. Administrators should consult the advisory for fixed versions and apply the vendor-provided updates to all affected products at or below version 10.97.3, as well as all versions of MC Works64.
Workarounds
- Use dedicated administrator accounts for each affected product rather than sharing a single administrator credential across installations
- Enforce multi-factor authentication (MFA) on all accounts with administrative access to engineering workstations and HMI servers
- Apply the principle of least privilege by relocating day-to-day operations to non-administrative accounts and auditing privileged account usage
# Review DCOM permissions on affected hosts
dcomcnfg
# Navigate: Component Services > Computers > My Computer > Properties > COM Security
# Review "Launch and Activation Permissions" and "Access Permissions" (Edit Default and Edit Limits)
# Remove or restrict entries that grant Local/Remote Launch and Activation to the product administrator account
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB