Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2025-55038 Overview
CVE-2025-55038 is an authorization bypass vulnerability in the AutomationDirect Click Plus C2-03CPU2 programmable logic controller (PLC) running firmware version 3.60. The flaw resides in the KOPR protocol used by the Remote PLC application. Authenticated users with low-level access permissions can read and modify PLC variables beyond their assigned authorization level. The weakness is tracked as Missing Authorization [CWE-862]. CISA published advisory ICSA-25-266-01 to coordinate disclosure for operators of affected industrial control systems.
Critical Impact
A low-privileged authenticated operator can tamper with PLC variables that control physical processes, undermining the integrity of industrial automation workflows.
Affected Products
- AutomationDirect Click Plus C2-03CPU2 PLC
- Firmware version 3.60
- Deployments using the Remote PLC application over the KOPR protocol
Discovery Timeline
- 2025-09-23 - CVE-2025-55038 published to NVD
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2025-55038
Vulnerability Analysis
The Click Plus C2-03CPU2 CPU module exposes PLC programming and runtime data through the KOPR protocol used by the Remote PLC application. The protocol authenticates users and assigns permission tiers, but it does not enforce those tiers on individual read and write operations against PLC variables. An authenticated low-privilege user can issue KOPR requests that modify data points reserved for higher-privilege roles. In an industrial environment, this allows operators or guest-tier accounts to alter setpoints, timers, counters, and output coils that drive physical equipment. The vulnerability affects integrity and confidentiality of process data without requiring code execution on the device.
Root Cause
The root cause is a missing authorization check [CWE-862] inside the KOPR request handler. The firmware validates that a session is authenticated but does not re-check the caller's permission level before servicing variable read and write operations. Permission enforcement is implicit rather than evaluated per operation.
Attack Vector
An attacker needs network reachability to the PLC and valid low-tier credentials. Attack complexity is high because the attacker must understand the KOPR protocol framing and target variable addressing. Once connected, the attacker crafts KOPR messages that reference restricted tags and submits them through the authenticated session to read sensitive values or push unauthorized writes.
No verified public proof-of-concept is available. See the CISA ICS Advisory ICSA-25-266-01 for vendor-coordinated technical details.
Detect Identity Attacks the Moment Authentication Fails
Singularity™ Identity surfaces credential misuse, lateral movement, and privilege escalation in real time, so you can contain the breach before it spreads.
Stop Identity AttacksDetection Methods for CVE-2025-55038
Indicators of Compromise
- Unexpected changes to PLC tag values, setpoints, or output coils that do not correlate with HMI operator actions or scheduled program logic.
- KOPR protocol sessions originating from engineering workstations or IP addresses that are not part of the approved control network inventory.
- Low-privileged user accounts issuing write operations against variables normally reserved for engineering or administrator roles.
Detection Strategies
- Baseline normal KOPR traffic patterns between the Remote PLC application and the C2-03CPU2 and alert on deviations in session frequency, source, or command type.
- Correlate PLC variable writes with authenticated user identity and flag writes performed by non-engineering accounts.
- Deploy an industrial protocol-aware intrusion detection sensor on the control network to parse KOPR traffic and surface anomalous requests.
Monitoring Recommendations
- Forward PLC authentication, session, and variable-change events to a centralized SIEM for long-term analysis and correlation with operator activity.
- Monitor firewall and VPN logs for new or unexpected connections into the operational technology (OT) segment hosting Click Plus controllers.
- Review process historian data for setpoint or output changes that lack a corresponding authorized HMI event.
How to Mitigate CVE-2025-55038
Immediate Actions Required
- Inventory all AutomationDirect Click Plus C2-03CPU2 devices and identify any running firmware 3.60.
- Restrict network access to the PLC so that only approved engineering workstations and the Remote PLC application server can reach the KOPR service.
- Rotate credentials for all low-tier PLC accounts and remove accounts that are no longer required.
- Audit recent PLC variable changes against operator and engineering logs to identify unauthorized modifications.
Patch Information
AutomationDirect publishes firmware and software updates through its Software Downloads portal. Review CISA ICS Advisory ICSA-25-266-01 for the vendor's remediation guidance and apply the firmware version identified in that advisory to the affected C2-03CPU2 modules.
Workarounds
- Place Click Plus controllers behind a dedicated OT firewall and block the KOPR service port from general enterprise and remote networks.
- Require VPN or jump-host access with multi-factor authentication for any user who needs Remote PLC application connectivity.
- Disable or remove low-privilege PLC accounts where business operations do not require them, following ISA/IEC 62443 least-privilege guidance.
# Example: restrict access to the PLC subnet at the OT firewall
# Replace addresses, interfaces, and ports with values specific to your environment
iptables -A FORWARD -s 10.20.30.0/24 -d 10.50.60.10 -p tcp --dport 25425 -j ACCEPT
iptables -A FORWARD -d 10.50.60.10 -j DROP
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB