Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2025-40817 Overview
CVE-2025-40817 affects Siemens LOGO! 8 BM devices and their SIPLUS variants across all firmware versions. The devices fail to perform required validations on incoming requests. An unauthenticated attacker on an adjacent network can change the device time, altering the behavior of time-dependent logic programs. The weakness is classified as Missing Authentication for a Critical Function [CWE-306]. Siemens documented the issue in Siemens Security Advisory SSA-267056.
Critical Impact
Unauthenticated adjacent-network attackers can modify the internal clock of Siemens LOGO! 8 BM controllers, causing time-based logic in industrial control programs to execute at attacker-chosen moments.
Affected Products
- Siemens LOGO! 12/24RCE, 12/24RCEo, 230RCE, 230RCEo, 24CE, 24CEo, 24RCE, 24RCEo (all versions)
- Siemens SIPLUS LOGO! 12/24RCE, 12/24RCEo, 230RCE, 230RCEo (all versions)
- Siemens SIPLUS LOGO! 24CE, 24CEo, 24RCE, 24RCEo (all versions)
Discovery Timeline
- 2025-11-11 - CVE-2025-40817 published to the National Vulnerability Database
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2025-40817
Vulnerability Analysis
Siemens LOGO! 8 BM controllers are compact programmable logic controllers used in building automation, small process control, and machine control. Time-of-day and date values inside the controller drive scheduled outputs, timers, and interlocks. The affected models accept time-setting operations over the network without validating the requester. An attacker with access to an adjacent network segment can issue a crafted request that modifies the device clock. Any function block that depends on wall-clock time (weekly timers, astronomical clocks, retentive on-delay behavior across restarts) then triggers according to the attacker's chosen time value. This can cause pumps, lights, HVAC actuators, and safety-adjacent interlocks to activate or remain off outside their intended windows.
Root Cause
The controllers omit authentication and integrity checks on the network handler that services time-set operations. Because no session, credential, or signed command is required, any station that can reach the LOGO! communication port on the local network can invoke the operation. The design defect maps to [CWE-306] Missing Authentication for Critical Function.
Attack Vector
Exploitation requires network adjacency to the target controller, typically the same Layer 2 broadcast domain or a routed OT segment reachable from a compromised engineering workstation, HMI, or IoT device. The attacker sends the vendor's time-set protocol message to the device. No user interaction, prior authentication, or exploit chaining is required. The impact is limited to integrity of the device state; confidentiality and availability of the controller itself are not directly affected by the primary flaw, though downstream physical processes may fail or run outside tolerance.
No public proof-of-concept exploit is currently listed for CVE-2025-40817. Refer to Siemens Security Advisory SSA-267056 for protocol-level details.
Stop Remote Code Execution Before It Runs
Singularity™ Endpoint detects and blocks exploit attempts at machine speed, including zero-days and novel attack techniques.
Stop Exploit AttemptsDetection Methods for CVE-2025-40817
Indicators of Compromise
- Unexpected changes in the LOGO! device real-time clock, particularly discrepancies between controller time and an authoritative NTP source.
- Timer- and schedule-driven outputs firing outside their documented operating windows.
- Diagnostic buffer entries on the LOGO! BM referencing time or date modification events from unknown source addresses.
Detection Strategies
- Passively monitor OT network segments for traffic to LOGO! communication ports originating from stations that are not authorized engineering workstations or HMIs.
- Correlate physical process anomalies (out-of-schedule actuation, missed cycles) with controller time drift recorded in historian data.
- Baseline expected clock-sync sources and alert when a LOGO! controller's time changes from any other origin.
Monitoring Recommendations
- Deploy an OT-aware intrusion detection sensor on segments hosting LOGO! 8 BM devices to log time-set commands.
- Forward controller diagnostic logs and network telemetry into a centralized SIEM or data lake for cross-source correlation.
- Periodically poll device time via a read-only monitoring account and alert on delta greater than an operationally acceptable threshold.
How to Mitigate CVE-2025-40817
Immediate Actions Required
- Restrict network access to LOGO! 8 BM devices to explicitly authorized engineering and HMI stations using firewall or VLAN segmentation.
- Place LOGO! controllers behind an industrial firewall or VPN gateway that enforces authentication before reaching the OT segment.
- Inventory all affected LOGO! 8 BM and SIPLUS LOGO! variants and confirm which are exposed beyond their trusted cell.
Patch Information
Siemens lists all versions of the identified LOGO! 8 BM and SIPLUS LOGO! models as affected, and no fixed firmware is documented in the referenced advisory at time of publication. Consult Siemens Security Advisory SSA-267056 for the latest remediation status and any subsequently released firmware.
Workarounds
- Follow Siemens' operational guidelines for LOGO! deployment in trusted, isolated networks and disable unused network services on the device.
- Enforce cell protection using a defense-in-depth architecture aligned with IEC 62443, including perimeter firewalls between OT and IT.
- Where feasible, avoid designing safety-relevant or high-consequence process logic that depends solely on the controller's internal clock without external validation.
# Example firewall rule (Linux iptables) restricting LOGO! TCP/102 access
# to a single authorized engineering workstation on the OT VLAN
iptables -A FORWARD -p tcp -d 10.20.30.40 --dport 102 \
-s 10.20.30.10 -j ACCEPT
iptables -A FORWARD -p tcp -d 10.20.30.40 --dport 102 -j DROP