Skip to main content
Vulnerability Database/CVE-2025-26383

CVE-2025-26383: iSTAR ICU Memory Leak Vulnerability

CVE-2025-26383 is a memory leak flaw in iSTAR Configuration Utility that exposes unauthorized data from Windows systems. This article covers technical details, affected versions, security impact, and mitigation strategies.

Published:

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

CVE-2025-26383 Overview

CVE-2025-26383 affects the Johnson Controls iSTAR Configuration Utility (ICU), a Windows tool used to configure iSTAR access control hardware. The utility leaks memory during operation, which can expose unauthorized data residing on the Windows host where ICU runs. The weakness is tracked as [CWE-457: Use of Uninitialized Variable], indicating that the application reads memory regions before properly initializing them. An adjacent-network attacker can observe the leaked contents and potentially harvest sensitive information from the host.

Critical Impact

Information disclosure from an uninitialized memory read in the iSTAR Configuration Utility can expose data from the Windows PC running ICU to adjacent-network observers.

Affected Products

  • Johnson Controls iSTAR Configuration Utility (ICU) on Windows
  • Deployments relying on ICU for iSTAR controller configuration
  • Workstations where ICU is installed and executed

Discovery Timeline

  • 2025-06-11 - CVE-2025-26383 published to the National Vulnerability Database
  • 2026-06-17 - Last updated in NVD database

Technical Details for CVE-2025-26383

Vulnerability Analysis

The iSTAR Configuration Utility leaks memory contents that should not be exposed to the network. The flaw is categorized under [CWE-457], meaning ICU uses variables or buffers before initializing them to known values. When these uninitialized regions are serialized into network responses or diagnostic outputs, residual process memory accompanies legitimate data. An attacker positioned on the same local or adjacent network segment can collect these fragments and reconstruct sensitive content. The exposure is limited to confidentiality; integrity and availability of the host are not directly impacted by this specific weakness.

Root Cause

The root cause is improper initialization of memory buffers before use within ICU. Fields intended to carry structured values instead contain stale heap or stack contents from previous allocations. Because ICU runs on a Windows PC that often holds operator credentials, configuration files, and controller secrets, the leaked bytes can include sensitive artifacts belonging to other processes or earlier ICU operations.

Attack Vector

Exploitation requires adjacent-network access to the Windows system running ICU. No authentication or user interaction is needed. An attacker interacts with ICU in a manner that triggers transmission of the uninitialized buffers, then captures and analyzes the responses to extract fragments of host memory. See the CISA ICS Advisory ICSA-25-146-01 and the Johnson Controls Security Advisory for vendor-supplied technical context.

// No verified proof-of-concept code is publicly available for CVE-2025-26383.
// Refer to the CISA and Johnson Controls advisories for implementation details.

Detection Methods for CVE-2025-26383

Indicators of Compromise

  • Unexpected ICU network traffic originating from or directed to workstations that host the utility.
  • Anomalous response sizes or payloads from ICU sessions that include non-printable or unrelated memory fragments.
  • Presence of unauthorized hosts on the management VLAN communicating with ICU endpoints.

Detection Strategies

  • Capture ICU network sessions and inspect responses for high-entropy or structurally anomalous content that suggests memory leakage.
  • Correlate workstation process telemetry with network flows to identify ICU interactions outside of authorized change windows.
  • Alert on new or rare peers initiating ICU protocol conversations with configuration workstations.

Monitoring Recommendations

  • Monitor the dedicated access control management network for unauthorized device enumeration or sniffing activity.
  • Track installation and execution of ICU.exe across the fleet and flag unapproved deployments.
  • Review authentication and session logs on hosts where ICU is used to detect lateral movement attempts following suspected exposure.

How to Mitigate CVE-2025-26383

Immediate Actions Required

  • Restrict ICU usage to isolated, trusted management networks that are not reachable from general corporate or guest segments.
  • Limit which workstations may run ICU and ensure those hosts contain no unrelated sensitive workloads.
  • Apply vendor updates from Johnson Controls as soon as they are available for your ICU version.

Patch Information

Johnson Controls publishes remediation guidance through its security advisory portal. Review the Johnson Controls Security Advisory and the CISA ICS Advisory ICSA-25-146-01 for the current patched version of ICU and installation instructions.

Workarounds

  • Segment the iSTAR management network using VLANs and firewalls to block adjacent-network reachability from untrusted zones.
  • Run ICU only on hardened, single-purpose workstations and shut down the utility when configuration tasks complete.
  • Enforce 802.1X or MAC-based access control on switch ports serving the ICU management segment to prevent unauthorized device attachment.
bash
# Example: restrict ICU host network exposure using Windows Firewall
# Allow ICU traffic only from the designated management subnet
netsh advfirewall firewall add rule name="ICU-Management-Only" ^
  dir=in action=allow program="C:\Program Files\Johnson Controls\ICU\ICU.exe" ^
  remoteip=10.10.50.0/24 profile=any

# Block ICU traffic from all other sources
netsh advfirewall firewall add rule name="ICU-Block-Other" ^
  dir=in action=block program="C:\Program Files\Johnson Controls\ICU\ICU.exe" ^
  remoteip=any profile=any

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB