Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2025-24510 Overview
CVE-2025-24510 affects the Siemens MS/TP Point Pickup Module across all versions. The device improperly handles specific incoming BACnet Master-Slave/Token-Passing (MSTP) messages. An attacker on the same BACnet network can send a specially crafted MSTP frame to trigger a denial of service condition on the targeted device. Recovery requires a manual power cycle, interrupting building automation operations until an operator physically intervenes. The vulnerability is tracked under [CWE-20: Improper Input Validation] and is documented in the Siemens Security Advisory SSA-668154.
Critical Impact
An adjacent-network attacker can crash the MS/TP Point Pickup Module with a single crafted BACnet MSTP message, requiring a manual power cycle to restore operation.
Affected Products
- Siemens MS/TP Point Pickup Module (All versions)
Discovery Timeline
- 2025-05-13 - CVE-2025-24510 published to the National Vulnerability Database (NVD)
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2025-24510
Vulnerability Analysis
The MS/TP Point Pickup Module fails to validate the structure or contents of certain incoming BACnet MSTP messages. BACnet MSTP is a serial communication protocol used over RS-485 for building automation devices such as HVAC controllers and sensors. When the firmware receives a malformed frame that falls outside expected parameters, the message handler enters an unrecoverable state. The device stops processing BACnet traffic and must be power-cycled to resume normal operation.
The flaw sits in the input validation layer of the MSTP parser, classified under [CWE-20]. Because MS/TP operates on a shared serial bus, every node on the segment can transmit frames to any other node. There is no cryptographic authentication at the MSTP layer, so an attacker with access to the bus can impersonate a legitimate participant.
Root Cause
The root cause is improper input validation of BACnet MSTP message fields. The firmware does not reject or safely discard frames with unexpected contents, allowing a single malformed message to disrupt device operation.
Attack Vector
Exploitation requires adjacent-network access to the BACnet MSTP segment hosting the vulnerable device. This typically means physical or logical access to the RS-485 bus, a compromised device already on the segment, or a BACnet router that bridges IP traffic onto the MSTP segment. No authentication, user interaction, or elevated privileges are required. The attacker transmits a crafted MSTP frame addressed to the vulnerable module, which then halts and requires a power cycle.
No public proof-of-concept exploit is available, and the vulnerability is not listed in the CISA Known Exploited Vulnerabilities catalog. The EPSS score is 0.258% as of October 2026.
Detection Methods for CVE-2025-24510
Indicators of Compromise
- MS/TP Point Pickup Module becomes unresponsive on the BACnet segment and resumes only after a manual power cycle.
- Unexpected gaps in BACnet polling data or alarm reporting from the affected device.
- Unusual or malformed MSTP frames observed on the RS-485 bus during BACnet traffic captures.
Detection Strategies
- Capture BACnet MSTP traffic using serial sniffers or BACnet-aware tools and inspect frames for malformed headers or unexpected PDU types directed at the module.
- Correlate device offline events in the building management system (BMS) with recent additions or activity from unauthorized MSTP nodes.
- Baseline the MAC address list of legitimate MSTP devices on each segment and alert on new or spoofed source addresses.
Monitoring Recommendations
- Enable BMS alerting for device communication loss and track power-cycle events on controllers hosting the Point Pickup Module.
- Deploy operational technology (OT) network monitoring at BACnet/IP routers that bridge to MSTP segments to detect suspicious frame patterns.
- Log and review physical access to panels, wiring closets, and controllers that terminate the RS-485 bus.
How to Mitigate CVE-2025-24510
Immediate Actions Required
- Review the Siemens Security Advisory SSA-668154 for the latest vendor guidance and fixed firmware availability.
- Inventory all MS/TP Point Pickup Modules deployed in building automation networks and identify their MSTP segments.
- Restrict physical and logical access to BACnet MSTP wiring, panels, and BACnet/IP routers that bridge to MSTP segments.
Patch Information
Siemens tracks remediation under advisory SSA-668154. Operators should consult the advisory directly for fixed firmware versions, interim fixes, and vendor-recommended configuration changes. Apply updates during planned maintenance windows and verify device operation afterward.
Workarounds
- Isolate BACnet MSTP segments from untrusted networks and limit BACnet/IP routing into MSTP segments where feasible.
- Enforce defense-in-depth per Siemens operational guidelines for industrial control systems, including network segmentation and firewall rules at the IT/OT boundary.
- Monitor for and physically secure all nodes on the RS-485 bus to prevent attachment of unauthorized MSTP devices.
# Example: segment BACnet/IP traffic at the IT/OT boundary firewall
# Replace interface names and subnets to match your environment
# Allow BACnet/IP (UDP 47808) only from authorized BMS workstations
iptables -A FORWARD -i eth_ot -p udp --dport 47808 -s 10.20.30.0/24 -j ACCEPT
iptables -A FORWARD -i eth_ot -p udp --dport 47808 -j DROP