Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB
CVE-2024-9876 Overview
CVE-2024-9876 is a Modification of Assumed-Immutable Data (MAID) vulnerability affecting ABB ANC, ANC-L, and ANC-mini industrial controllers. The flaw, classified under [CWE-471], allows an attacker with low privileges on an adjacent network to alter data the firmware treats as immutable. Successful exploitation compromises the confidentiality and integrity of the affected device. ABB ANC, ANC-L, and ANC-mini versions through 1.1.4 are affected. The vulnerability carries an EPSS probability of 0.25%.
Critical Impact
An authenticated attacker on an adjacent network can modify assumed-immutable configuration or firmware data on ABB ANC devices, undermining device integrity and exposing sensitive control-system data.
Affected Products
- ABB ANC through version 1.1.4
- ABB ANC-L through version 1.1.4
- ABB ANC-mini through version 1.1.4
Discovery Timeline
- 2025-04-30 - CVE-2024-9876 published to NVD
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2024-9876
Vulnerability Analysis
The vulnerability resides in the ABB ANC family of controllers, which process data assumed by the firmware to be immutable without validating that assumption at runtime. An attacker who gains low-privileged access on an adjacent network segment can modify this protected data. Because the firmware trusts the data implicitly, modifications propagate into control decisions and configuration state without triggering integrity checks. The impact is restricted to the affected device scope and does not extend to subsequent systems.
Root Cause
The root cause is improper enforcement of data immutability, categorized under [CWE-471] (Modification of Assumed-Immutable Data). The firmware reads values from writable storage or an exposed interface but handles those values as if they were read-only. No cryptographic signature, hash, or write-protection mechanism prevents an authenticated adjacent-network actor from changing the data between validation and use.
Attack Vector
Exploitation requires adjacent-network access to the ANC device along with low-level authenticated credentials. No user interaction is needed. Once reachable, the attacker sends crafted requests to update fields the controller assumes cannot change post-provisioning. These typically include firmware-tagged configuration blocks, calibration data, or operational parameters exposed through the device management interface. No public proof-of-concept or exploit code is available at this time. Refer to the ABB Security Advisory for vendor-specific technical details.
Detection Methods for CVE-2024-9876
Indicators of Compromise
- Unexpected changes to ANC device configuration, calibration, or firmware-tagged parameter blocks outside planned maintenance windows.
- Authenticated management sessions originating from unexpected hosts on the control-system VLAN.
- Device log entries indicating writes to parameters normally set only during commissioning.
Detection Strategies
- Baseline the expected configuration of each ANC, ANC-L, and ANC-mini device and compare periodically to detect drift.
- Monitor the industrial network for management protocol traffic directed at ANC devices from non-engineering workstations.
- Correlate device-side audit logs with network flow records to attribute configuration changes to a specific session.
Monitoring Recommendations
- Forward ANC device logs and OT network telemetry to a centralized analytics platform such as Singularity Data Lake for retention and correlation.
- Alert on write operations to parameters flagged as immutable by the asset owner.
- Track authentication events on ANC management interfaces and flag off-hours or repeated low-privilege logins.
How to Mitigate CVE-2024-9876
Immediate Actions Required
- Inventory all ABB ANC, ANC-L, and ANC-mini devices and identify units running firmware 1.1.4 or earlier.
- Restrict management access to ANC devices to a dedicated engineering VLAN with strict access control lists.
- Rotate credentials used to authenticate to the ANC management interface and remove any shared low-privilege accounts.
- Review device audit logs for unauthorized configuration changes prior to patching.
Patch Information
ABB has published guidance in advisory document 2CRT000006. Apply the firmware release that supersedes version 1.1.4 as described in the ABB Security Advisory. Confirm firmware integrity after upgrade and re-baseline device configuration.
Workarounds
- Segment ANC devices behind an industrial firewall and block adjacent-network access from non-engineering zones.
- Enforce multi-factor authentication on jump hosts used to reach ANC management interfaces.
- Disable unused management protocols and services on each ANC device.
- Implement change-control procedures that log and approve every parameter write to affected controllers.
# Example firewall rule restricting ANC management access to the engineering subnet
iptables -A FORWARD -s 10.10.20.0/24 -d 10.50.0.0/24 -p tcp --dport 502 -j ACCEPT
iptables -A FORWARD -d 10.50.0.0/24 -p tcp --dport 502 -j DROP
Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.
Sources: National Vulnerability Database, CISA KEV, Exploit-DB