Skip to main content
Vulnerability Database/CVE-2024-52285

CVE-2024-52285: SiPass Integrated Information Disclosure

CVE-2024-52285 is an information disclosure vulnerability in SiPass integrated AC5102 and ACC-AP devices that exposes MQTT URLs without authentication. This post explains its impact, affected versions, and mitigation steps.

Published:

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

CVE-2024-52285 Overview

CVE-2024-52285 affects Siemens SiPass integrated access control devices. The vulnerability stems from Missing Authentication for Critical Function [CWE-306] in the MQTT (Message Queuing Telemetry Transport) interface. Affected devices expose several MQTT URLs without authentication, enabling unauthenticated remote attackers to access sensitive data over the network.

Siemens published advisory SSA-515903 identifying the issue in SiPass integrated AC5102 (ACC-G2) and SiPass integrated ACC-AP, with all firmware versions below V6.4.8 vulnerable. The flaw requires no privileges, no user interaction, and is exploitable over the network.

Critical Impact

Unauthenticated remote attackers can retrieve sensitive data from exposed MQTT endpoints on affected SiPass integrated access control hardware.

Affected Products

  • Siemens SiPass integrated AC5102 (ACC-G2) — all versions prior to V6.4.8
  • Siemens SiPass integrated ACC-AP — all versions prior to V6.4.8
  • Associated SiPass integrated deployments running vulnerable firmware

Discovery Timeline

  • 2025-03-11 - CVE-2024-52285 published to NVD
  • 2026-06-17 - Last updated in NVD database

Technical Details for CVE-2024-52285

Vulnerability Analysis

The vulnerability resides in the MQTT broker interface exposed by SiPass integrated access controllers. MQTT is a lightweight publish-subscribe protocol commonly used for machine-to-machine and IoT communication. On affected devices, several MQTT URLs are reachable without any authentication handshake.

An attacker with network access to the controller can subscribe to exposed topics and retrieve data flowing through the broker. The exposed data concerns the operation of the access control system, which may include device state and configuration-related information. The flaw is categorized under CWE-306: Missing Authentication for Critical Function.

Root Cause

The SiPass integrated firmware ships MQTT endpoints without enforcing client authentication. The MQTT specification supports username and password credentials and TLS client certificates, but the vulnerable firmware does not require either. Any network-reachable client can connect and subscribe to topics the broker exposes.

Attack Vector

Exploitation requires network reachability to the controller's MQTT service, typically TCP port 1883. An attacker uses a standard MQTT client to connect, subscribe to wildcard topics such as #, and passively collect published messages. No credentials, prior access, or user interaction are needed. The attack produces confidentiality impact only, with no documented integrity or availability consequences.

Further technical details are available in Siemens Security Advisory SSA-515903.

Detection Methods for CVE-2024-52285

Indicators of Compromise

  • Unexpected MQTT CONNECT packets to SiPass controllers from unknown source IP addresses
  • MQTT SUBSCRIBE requests using wildcard topic filters (# or +) against controller brokers
  • Long-lived MQTT sessions from hosts outside the operational technology (OT) management segment

Detection Strategies

  • Inspect network traffic on TCP port 1883 for MQTT activity originating outside the authorized management network
  • Audit SiPass integrated firmware versions and flag any device running a release prior to V6.4.8
  • Correlate asset inventory with network flows to identify controllers exposing MQTT services to broader networks

Monitoring Recommendations

  • Deploy network sensors on OT segments hosting SiPass controllers and alert on MQTT connections from unapproved subnets
  • Log firewall denies for MQTT ports to detect reconnaissance against access control devices
  • Baseline normal MQTT publisher and subscriber identities and alert on deviations

How to Mitigate CVE-2024-52285

Immediate Actions Required

  • Update SiPass integrated AC5102 (ACC-G2) and ACC-AP firmware to version V6.4.8 or later
  • Restrict network access to the MQTT service so only authorized management hosts can reach the controller
  • Place SiPass controllers in a dedicated, segmented OT network isolated from general corporate traffic

Patch Information

Siemens released firmware version V6.4.8 for both SiPass integrated AC5102 (ACC-G2) and SiPass integrated ACC-AP. Apply the update through standard SiPass integrated maintenance procedures. Refer to Siemens Security Advisory SSA-515903 for firmware download links and version verification.

Workarounds

  • Block external access to MQTT ports (default TCP 1883 and 8883) at the perimeter firewall
  • Enforce access control lists on switches that only permit designated management workstations to reach controllers
  • Monitor controller network interfaces for unauthorized MQTT connection attempts until patching is complete

Disclaimer: This content was generated using AI. While we strive for accuracy, please verify critical information with official sources.

Sources: National Vulnerability Database, CISA KEV, Exploit-DB

Experience the Most Advanced Cybersecurity Platform

See how the world’s most intelligent, autonomous cybersecurity platform can protect your organization today and into the future.