CVE-2024-10498 Overview
CVE-2024-10498 is a memory buffer boundary vulnerability [CWE-119] affecting a Schneider Electric device exposing a Modbus interface. An unauthenticated attacker on the network can send crafted Modbus write packets that modify configuration values outside the expected range. Successful exploitation can corrupt device configuration data or disable the web management interface. The flaw is remotely reachable with low attack complexity and requires no user interaction, making it relevant for industrial networks where Modbus is exposed.
Critical Impact
Unauthenticated remote attackers can send malformed Modbus write packets to force out-of-range configuration values, resulting in invalid device state or loss of web interface functionality.
Affected Products
- Schneider Electric device referenced in security notice SEVD-2025-014-08
- Modbus-enabled firmware versions listed in the vendor advisory
- Operational technology deployments exposing the Modbus TCP service
Discovery Timeline
- 2025-01-17 - CVE-2024-10498 published to NVD
- 2026-06-17 - Last updated in NVD database
Technical Details for CVE-2024-10498
Vulnerability Analysis
The vulnerability stems from improper restriction of operations within the bounds of a memory buffer when the device processes incoming Modbus write function codes. The firmware accepts write requests that target configuration registers without validating that the supplied values fall inside documented operational ranges. When out-of-range values are written, the device stores them in configuration memory and subsequently references them during normal operation.
The downstream effects include invalid runtime state and failure of the web interface that administrators rely on for monitoring and configuration. Loss of the management plane complicates incident response and recovery because operators lose visibility and remote control of the device.
Root Cause
The root cause is missing bounds validation on Modbus register write handlers. The firmware trusts client-supplied values and writes them directly to configuration storage without range or sanity checks defined by the data model.
Attack Vector
An attacker with network reachability to TCP port 502 (or the serial Modbus channel bridged to IP) can craft Modbus function code 06 (Write Single Register) or function code 16 (Write Multiple Registers) packets. No authentication is required because the Modbus protocol does not enforce it. The attacker iterates values that exceed documented register ranges to corrupt configuration state. Technical details are available in the Schneider Electric Security Notice SEVD-2025-014-08.
Detection Methods for CVE-2024-10498
Indicators of Compromise
- Unexplained loss of the device web interface or management portal availability
- Configuration register values that fall outside vendor-documented operating ranges
- Modbus write requests originating from hosts outside the engineering workstation subnet
- Spikes in Modbus function codes 06 and 16 directed at a single device
Detection Strategies
- Deploy OT-aware network monitoring that parses Modbus TCP and alerts on write operations to protected register ranges
- Baseline normal Modbus traffic patterns and alert on deviations in source address, register targets, or payload values
- Correlate web interface outages with preceding Modbus write activity on the same device
Monitoring Recommendations
- Capture full packet traces on TCP port 502 at the Purdue Level 2/3 boundary for forensic review
- Forward device syslog and controller event logs to a central SIEM for correlation with network telemetry
- Audit configuration register values on a scheduled basis and compare against a known-good baseline
How to Mitigate CVE-2024-10498
Immediate Actions Required
- Review the Schneider Electric Security Notice SEVD-2025-014-08 and apply the referenced firmware update
- Restrict Modbus TCP (port 502) access to authorized engineering workstations using firewall rules or ACLs
- Place affected devices behind an OT firewall that enforces deep packet inspection for Modbus
Patch Information
Schneider Electric has published remediation guidance in security notice SEVD-2025-014-08. Operators should consult the advisory for the specific product models, affected firmware versions, and fixed releases, then schedule patch deployment during a maintenance window to avoid process disruption.
Workarounds
- Segment OT networks from IT and corporate zones per IEC 62443 zone and conduit guidance
- Disable the Modbus service on devices where it is not operationally required
- Enforce VPN or jump host access for any remote engineering activity targeting Modbus devices
- Monitor for and block Modbus write requests from unauthorized source addresses at the perimeter
# Example firewall rule restricting Modbus TCP access to authorized hosts
iptables -A INPUT -p tcp --dport 502 -s 10.10.20.0/24 -j ACCEPT
iptables -A INPUT -p tcp --dport 502 -j DROP